R-IS-0201M-A, external SSR control moduleTXN 142 17.A
R-IS-0201M-A; RFox2, 2x AI / DI, 1x AO / PWM- for control of external SSR, 1f, radio type A
DI | |
---|---|
DO | 1x DO (PWM) |
AI | 2x AI |
AO | 1x AO |
COM | 1x RFox2 slave |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
R-IS-0201M-A, external SSR control module |
R-IS-0200M-A; RFox2, 2x AI / DI, 1x AO / PWM- for external SSR control, 1f, type A radio
Order num. | TXN 142 17.A |
---|---|
Teco code | TXN 142 17.A |
Categories | RFox2 - DIN Rail Modules |
Tags | - |
COM - Wireless network | |
---|---|
RFox2 wireless network | RFox2 Slave |
Communication frequency band | 868,1 MHz |
Transmission power | +14 dBm |
Input sensitivity | –108 dBm |
Modulation type | 2-GFSK |
Communication speed | 50 kbps |
DO - Parameters of binary transistor outputs (group A) | |
Parameters valid for the terminals | GND, PWM (C2, C3) |
Number of transistor outputs | 1 |
Number of output groups | 1 |
Number of outputs in group | 1 |
Output type | MOSFET (High-side switch) |
Switching current, output load | 20 mA max. |
Special functions (A) | PWM |
Operating frequency | 1 Hz - 1 kHz |
Alternation settings | 0 – 100 % |
AI - Analog Input Ranges (Group A) | |
Parameters valid for inputs on the terminals | AI1, AI2, GND (B3, B2, B1) |
Passive sensor | Pt1000, W100 = 1,391 (-90 to +400 ° C) |
Resistance measurement error - temperature coefficient | 3850 ppm / °C |
AO - Analog output parameters | |
Number of outputs in group | 1 |
Parameters valid for the terminals | AO (C1), GND (B1) |
Common wire of group | GND terminal |
Voltage output - voltage | 0 - 10 V |
Voltage output - maximum output current | 10 mA |
Power supply | |
Supply voltage, tolerances | 90 – 270 V AC |
Input voltage frequency | 50-60 Hz |
Maximum power input | 2 W |
Galvanic separation of power supply from internal circuits | No |
Insulation voltage of galvanic separation | 3 000 VDC |
Internal protection | Yes, non-refundable |
Size and weight | |
Weight approx. | 75 g |
Module width in multiples of M (17.5 mm) | 1M |
Product dimensions (width x height x depth) | 18 x 95 x 58 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes) |
Protection class of electrical object | II, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP20 |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | Module on DIN rail |
Working position | Vertical |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | -20 °C to + 55 °C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015) |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.3: 2012 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Connection | |
Connection description | An example of module connection is shown in the following figure. Any type designed for the 868 MHz band with an SMA connector (pin) can be used as an antenna. |
Warnings / Cautions | CAUTION: The device contains parts with dangerous voltage, disconnect the relevant circuits or switch off the power supply before removing the covers or handling the wiring! |
Connection of power and system communication | terminal block with screw terminal 2.5 mm2 |
Connection of inputs / outputs | terminal block with screw terminal 2.5 mm2 |
Module operation | |
Commissioning | The module is operated in the RFox2 radio network as a peripheral module, the settings are made in the Mosaic programming environment project manager, see the TXV 003 93 manual with the description of RFox2Lib. |
Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. |
Instructions | Because the module contains semiconductor components, it is necessary to follow the principles for working with components sensitive to electrostatic charge during repairs. Repairs are performed exclusively by the manufacturer's service center or the manufacturer's authorized service. |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
R-IS-0201M.A - Basic documentation
148.10 kB
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
- R-IS-0201M-A_kopie491 - The R-IS-0201M-A module is designed primarily for continuous power control of el. heating, eg for continuous power control of the electric cartridge in the DHW storage tank. The module is equipped with one active PWM output, eg for SSR control for c...
- R-IS-0201M-A - The R-IS-0201M-A module is designed primarily for continuous power control of el. heating, eg for continuous power control of the electric cartridge in the DHW storage tank. The module is equipped with one active PWM output, eg for SSR control for c...
No data available.