IB-7310TXN 173 10
IB-7310 64xDI, GO, for external modules IB-04xx
DI | 64x DI |
---|---|
DO | |
AI | |
AO | |
COM | 1x TCL2 |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
IB-7310 |
The IB-7310 module is designed for reading up to 64 binary 24 V DC signals with a common minus terminal, Type 3. The module is equipped with four connectors, each with 16 inputs, to which voltage is supplied from an external 24 V DC supply voltage source. .
These inputs are designed primarily for connecting external modules of the IB-04xx series. External modules IB-04xx are structurally adapted for installation on a DIN rail. For the IB-7310 module, they unify binary signals from different voltage levels and integrate the protections of these inputs.
These inputs are designed primarily for connecting external modules of the IB-04xx series. External modules IB-04xx are structurally adapted for installation on a DIN rail. For the IB-7310 module, they unify binary signals from different voltage levels and integrate the protections of these inputs.
Order num. | TXN 173 10 |
---|---|
Teco code | TXN 173 10 |
Categories | TC700 - I / O Expansion Modules |
Tags | Sales and production discontinued |
COM - System buses | |
---|---|
TCL2 - system I/O bus | 1x TCL2 slave |
DI - Organization of binary inputs | |
Total number of binary inputs | 64 |
Number of groups of binary inputs | 8 |
Organization of binary inputs into groups |
8x DI(DI0-DI7) + 8x DI(DI8-DI15) + 8x DI(DI16-DI23) + 8x DI(DI25-DI31) + 8x DI(DI32-DI39) + 8x DI(DI40-DI47) + 8x DI(DI48-DI55) + 8x DI(DI56-DI63) |
DI - Parameters of binary inputs DC (group A) | |
Parameters valid for inputs on the terminals | DI0 - DI63 |
Number of inputs in group | 8 |
Common wire | minus |
Input type | Type 3 (IEC) |
Galvanic isolation of inputs from internal/peripheral circuits | Yes, even between groups |
Diagnostics | indication of energized input by LED on module panel |
Input voltage for log. 0 | 0 V DC; -15 V DC min; 5 V DC max. |
Input voltage for log. 1 | 24 V DC; 15 V DC min.; 30 V DC max. |
Input current at log. 1 (typ.) | 3 mA |
Delay from log. 0 to log. 1 | 5 ms |
Delay from log. 1 to log. 0 | 5 ms |
Insulation voltage between inputs and internal circuits | 500 V |
Insulation voltage between groups of inputs | 500 V |
Power supply | |
Nominal supply voltage (V) | 24 V DC; Power supply from the system bus |
External power supply of input circuits - voltage | 24 V DC/AC |
Current consumption of one group from an external source, max. | 30 mA |
Power consumption from the system source | 1,5 W |
Size and weight | |
Weight approx. | 300 g |
Product dimensions (width x height x depth) | 30 x 198 x 137 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units |
Protection class of electrical object | III, ČSN 33 0600: 1995 |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP20 |
Operating areas | Normal, according to ČSN 33 2000-3: 1995 (mod IEC 364-3: 1993) |
Degree of pollution | 2, according to ČSN EN 61131-2 |
Overvoltage category installation | II according to ČSN 33 0420-1 |
Type of device | Built-in |
Working position | Vertical |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | 0 ° C to + 55 ° C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | A, according to EN 55022: 1999 (mod CISPR22: 1997) |
Emmisions - note | In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action. |
Electromagnetic compatibility / Immunity | min. as required by EN 61131-2: 2007 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Installation | |
Assembly description | The installation of the module into the supporting frame of the TC700 system is performed according to TXV 004 02. The mechanical dimensions are given in the TXV 004 02 documentation. |
Connection | |
Connection of inputs / outputs | IDC connector for flat cables, plug with pull-out mechanism |
Module operation | |
Module configuration | The module is operated, set up and diagnosed from the Mosaic development environment. |
Commissioning | After inserting the module into the frame and switching on the power supply, it is fully ready for operation and no other elements are set on it. |
Module diagnostics | The basic diagnostic system of the module is a part of its standard software. It operates from module power on and operates independently of the user. Diagnostic error states of the module and connected peripheral modules of the assembly are signaled |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
IB-7310 - Basic Documentation
179.67 kB, (CS, EN)
TC700 connectors - Basic documentation
105.65 kB
- IB–7310 binary input module - The IB-7310 module is designed for scanning of up to 64 binary signals 24 VDC with minus common pole, type 3 and it is designed primarily for the connections of external module to a DIN bar of series IB-04xx. The module is fitted with four connector...
- DIGITAL INPUT MODULE IB-0404 - ...a common minus terminal from the controlled technology and their transfer to the control system module (eg connection to the IB-7310, IB-7311, and IS-7510 system modules TC700). The module is equipped with a terminal block with spring contacts, the s...
- DIGITAL INPUT MODULE IB-0403 - ...h a common terminal from the controlled technology and their transfer to the control system module (eg connection to modules IB-7310, IB-7311, and IS-7510 of the TC700 system). The module is equipped with a terminal block with spring contacts, each i...
- DIGITAL INPUT MODULE IB-0402 - ...ith a common minus terminal from the controlled technology and their transfer to the control system module (eg connection to IB-7310, IB-7311, and IS-7510 system modules TC700). The module is equipped with a terminal block with spring contacts, each...
- DIGITAL INPUT MODULE IB-0401 - ...s with direct connection of two-wire or three-wire sensors and their transfer to the control system module (eg connection to IB-7310, IB-7311, and IS-7510 system modules TC700). The module is equipped with a terminal block with spring contacts and th...
No data available.