C-WS-0001R-T2-8SHNTXN 143 24.T2.8SHN

C-WS-0001R-T2-8SHN, CIB, touch controller, 8 buttons, white backlight, display 1", 2 AI, sensor T+RH, black

DI 8 buttons
DO
AI 2x AI
AO
COM 1x CIB slave
SENSOR Temperature
Humidity
Picture Variant Variant description
C-WS-0001R-T2-8SHN
C-WS-0001R-T2-8NHN
C-WS-0001R-T2-8NHN, CIB, wall-mounted glass touch controller, 8 capacitive buttons, spot backlight R+G, without display, sensor T+RH, black
Order num. TXN 143 24.T2.8SHN
Teco code TXN 143 24.T2.8SHN
Categories CFox - Touch Controllers C-WS-0001R
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
DI - Organization of binary inputs
Total number of binary inputs 8
Organization of binary inputs into groups 8 capacitive buttons
AI - Organization of analog inputs
Total number of analog inputs 2
Number of inputs per group 2
Number of analog input groups 1
Organization of analog inputs into groups 2x AI (AI1, AI2)
Common wire AGND clamp
Galvanic separation from internal circuits No
AI - Analog Input Ranges (Group A)
Voltage 0-2 V
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Pt1000, W100 = 1,391 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Ni1000, W100 = 1.617 (-60 to +200 ° C)
Passive sensor Resistance transmitter 0-100 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
Parameter des Temperatursensors
Temperature - Measurement range –20 °C ÷ +70 °C
Temperature - Resolution 0,1 °C
Temperature - Measurement accuracy typ. ±0,5 °C
Humidity sensor parameters
Relative humidity - Resolution 0,1 % RH
Relative humidity - Measurement accuracy ±4 %
Power supply
Supply voltage, tolerances 24 V DC, +25%, -15%, SELV
Power supply from CIB - voltage 24/27 V DC
Maximum power input 1,2 W
Maximum current consumption (mA) < 30 mA
Galvanic separation of power supply from internal circuits No
Internal protection No
Size and weight
Product dimensions (width x height x depth) 94 x 94 x 17 mm, 12 mm above the wall
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed.4 :2017 (EN 60730-1:2016) -Automatic electronic control device (for household and similar purposes)
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP40 front, IP00 rear
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device On the wall
Working position Vertical
Type of operation (operating frequency) Continuous
Operating temperature maximum (° C) +70°C
Operating temperature minimum (° C) -20°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 ° C to + 85 ° C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.3: 2012
Sinusoidal vibration endurance 10 Hz to 57 Hz amplitude 0.075 mm, 57 Hz to 150 Hz acceleration 1 G, according to Fc according to ČSN EN 60068-2-6 ed.2:2008 (idt IEC 60068-2-6:2007), 10 cycles in each axis .
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description Installation on the wall in the interior using an installation box (73 mm).
Connection
Power connection Via the system bus
CIB connection Push-In terminal 0.3 - 1 mm2
Module operation
Commissioning The module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-WS-0001R-T2.8 - Basic documentation

2.62 MB, (EN)

No data available.

No data available.