C-IT-0200R-LOGUS goldTXN 133 20.LTDU

C-IT-0200R-LOGUS gold; CIB, Indoor temperature sensor, 2x temperature (1x internal, 1x external)

DI
DO
AI 1x AI (NTC12k, 0-100kΩ)
AO
COM 1x CIB slave
SENSOR 1x Temperature
C-IT-0200R-LOGUS; CIB, Indoor temperature sensor, 2x temperature (1x internal, 1x external), white
Order num. TXN 133 20.LTDU
Teco code TXN 133 20.LTDU
Categories CFox - LOGUS, Covers and devices
Tags -
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB slave
AI - Analog Input Ranges (Group C)
Parameters valid for inputs on the terminals +IN, -IN
Passive sensor NTC Thermistor 12k / 25 °C (-40 to + 125 °C)
Resistance measurement error - maximum error at 25 ° C ± 0.5% of full scale
Parameter des Temperatursensors
Temperature - Measurement range 0°C ÷ 50°C
Temperature - Resolution 0,1 °C
Temperature - Measurement accuracy typ. ±0,5 °C
Power supply
Supply voltage, tolerances 24/27 V DC from CIB bus
Typical power input 0,3 W
Maximum power input < 0,5 W
Galvanic separation of power supply from internal circuits No
Internal protection Yes, PTC reversible fuse
Size and weight
Weight approx. 75 g
Product dimensions (width x height x depth) 56 x 26 x 16 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP10B
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device In the installation box on the wall
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55022: 1999 (mod CISPR22: 1997)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description Indoor wall mounting
Connection
Connection description The module is implemented as a standard unit on a two-wire CIB bus, which ensures communication and power supply of the entire sensor. The bus wires are connected to the wires that are routed on the tube module (see Fig. 2).

The CIB bus can have any topology and branching up to a distance of 500 m and up to 32 units on one CIB branch. The CIB bus master is the basic PLC unit TECOMAT FOXTROT or an external CIB bus master, eg the CF-1141 module. Further information can be found in the manual Peripheral modules on the CIB TXV 004 13.
Assembly C-IT-0200R-Design:
1. Tube module
2. Temperature sensor in selected interior design
Connection of power and system communication Loose wires in the connector / 0.15-0.5 mm2
Module connection Assembly and installation instructions C-IT-0200R-Design:
1. Connect the module to the CIB bus.
2. Connect an external sensor (if used) to the appropriate wires of the tube module.
3. Slide the temperature sensor connector onto the tips of the tubing module.
4. Insert the tube module into the installation box. Be careful not to disconnect the temperature sensor connector from the tube module.
5. Attach the temperature sensor design to the installation box
Module operation
Module configuration The module is operated, set up and diagnosed from the Mosaic development environment.
Commissioning The module is ready for operation after connecting the CIB supply voltage. HW address of the relevant
module is indicated on the type plate.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

C-IT-0200R-Design - Basic documentation

71.33 kB

User manuals

PDF

Peripheral modules on the CIB Common Installation Bus(R) (en), TXV00413_02

13.94 MB, (EN, RU, DE, UA)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot - EC Declaration of conformity

295.20 kB, (EN, RU, DE, UA)

No data available.