KB-0552TXN 105 52
KB-0552, Converter TCL2 (RS-485) / MM optical fiber
DI | |
---|---|
DO | |
AI | |
AO | |
COM | 1x TCL2 1x Optic fibre multimode |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
KB-0552 |
RS-485 or TCL2 bus connection module for connection with multimode optical cables with 'ST' type optical connectors. TXN 105 52 contains 1 piece of module for connecting a duplex glass optical cable 62.5 / 125 4m or 50/125 4m up to a distance of 1750 m.
Order num. | TXN 105 52 |
---|---|
Teco code | TXN 105 52 |
Categories | Foxtrot - Communication Modules (TCL2) |
Tags | - |
COM - System buses | |
---|---|
TCL2 - system I/O bus | 1x TCL2 slave |
Power supply | |
Supply voltage, tolerances | 24 V DC, +25%, -15%, SELV |
Typical power input | 1 W |
Size and weight | |
Weight approx. | 75 g |
Module width in multiples of M (17.5 mm) | 1M |
Product dimensions (width x height x depth) | 17,7 x 95,3 x 75 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 61131-2: 2005 (idt IEC61131-2: 2003) - Programmable control units |
Protection class of electrical object | III, according to ČSN EN 61140: 2003 (idt IEC 61140: 2001) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP10B |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Type of device | Module on DIN rail |
Working position | Vertical |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | 0 ° C to + 55 ° C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | A, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015) |
Electromagnetic compatibility / Immunity | min. as required by EN 61131-2: 2007 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
Files for designers
KB-0552
73.66 kB
HW documentation
KB-0552 - Basic documentation
108.23 kB
EC - Declaration of Conformity
Foxtrot - EC Declaration of conformity
295.20 kB, (EN, RU, DE, UA)
- Connecting peripheral FOXTROT modules by fibre-optic cable, the KB-0552 module - The KB-0552 modules for fibre-optic connection are designed to connect fibre-optic cables with the ST type of optical connectors. The module does not contain termination of the TCL2 metallic bus (the 120 Ω resistor), so it does not have to be...
- Power dissipation of modules for calculation of switchboard heating - ...Power supply 230VAC/27,2VDC, 2,2A; 12VDC 0,3A PS2-60/27 10,0 W TXN 105 52 KB-0552, TCL2 Converter MM fiber optic - 1 piece KB-0552 1,2 W TXN 110 00 C...
- TCL2 bus installation - ...tic cables or a combination of fibre-optic and metallic cables. For fibre-optic cable connection it is necessary to use the KB-0552 optical converter (for the wiring see Chapter 3.3.5 ). The modules should be connected via standard ST-ST patch c...
No data available.