The PW-8901 is a power supply module in a 24 mm wide housing that generates two power supply voltages on the TC800 system bus from the 24 V DC network: VM for powering the internal circuits of the modules and VIO for powering the input circuits of selected modules. At the same time, it enables the connection of multiple frames via the TCL3 system bus. The connectors are screwless.
Order num. TXN 189 01
Teco code TXN 189 01
Categories TC800 - Power supply modules
Tags -
Power supply
Nominal supply voltage (V) 24 V DC
Supply voltage, tolerances 20 - 30 V DC
Maximum input current Ivm 5 A
Maximum input current Ivio 6 A
Module thermal/power loss 1 W
Bridging a power failure 10 ms min.
Integrated UPS function No
Isolation voltage between VM, VIO and TCL3 500 V
Size and weight
Weight approx. 100 g
Product dimensions (width x height x depth) 24 x 118 x 97 mm
Operating conditions, product standards
Product standard ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical object III, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 2, according to ČSN EN 60664-1 ed.2: 2008 (idt IEC 60664-1: 2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Built-in
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures -20 °C to + 55 °C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Storage relative humidity Max. 80% without vapor condensation
Storage environment Dry, clean areas without conductive dust, aggressive gases or acid vapors for a period not exceeding the warranty period.
Transport temperatures -25°C to -70°C
Transport environment Covered means of transport, transport packaging must not be exposed to the effects of rain and snow
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Electromagnetic compatibility / Immunity min. as required by EN 61131-2: 2007
Sinusoidal vibration endurance 10 Hz to 57 Hz amplitude 0.075 mm, 57 Hz to 150 Hz acceleration 1 G, according to Fc according to ČSN EN 60068-2-6 ed.2:2008 (idt IEC 60068-2-6:2007), 10 cycles in each axis .
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The installation of the TC800 system module is carried out by sliding it perpendicularly onto the DIN rail ČSN EN 50022 with busbar and locking latch in the lower part of the module. A more detailed description and mechanical drawings with dimensions are given in the documentation TXV 004 72.
Connection
Power connection terminal block with spring terminal 1.5 mm2, push-in
Connection description An example of module connection is shown in the following figure.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

PW-8901 - basic documentation (en)

1.46 MB, (EN)

Files for designers

ZIP

TC800 - library of elements in DXF and DWG formats, v. 2024/01

487.65 kB
KNI

TC800 - element library for SchemataCAD, v. 2024/01

116.21 kB

EC - Declaration of Conformity

PDF

TC800 - CE declaration of conformity (cs)

292.20 kB
PDF

TC800 - CE Declaration of Conformity (en)

709.29 kB
  • Power supply modules PW-8901 and PW-8902 - The PW-8901 power supply module is designed to power TECOMAT TC800 PLC assemblies from a 24 V DC network in a 24 mm wide case. It is a module that provides power for internal circuits (VM) and IO circuits (VIO) with an output level of 24 V SELV (c...
  • Examples of power connections for TC800 modules - ...s article describes the correct examples of powering the modules (both internal and IO circuits) of the TC800 system. The PW-8901 power supply module has two power level inputs VM and VIO on connector A. We connect the 24 VDC supply voltage to...
  • TC800 power supply sizing calculation and heat loss - ...nbsp;             PW-8901 TXN 189 01 2 0,8 W 0,1 W 3,2 W 1) 3,2 W 1)...
  • TECOMAT TC800 SYSTEM FEATURES - ...rticle  CENTRAL MODULES TC800 . Basic overview of TC800 modules Central module CP-8001 Power supply modules PW-8901 and PW-8902 Binary input module IB-8302 Binary input module IB-8310 Binary output module OS-8401...

No data available.