IB-7302TXN 173 02

IB-7302 32 inputs 24 V  DC / 5 ms

DI 32x DI
DO
AI
AO
COM 1x TCL2
SENSOR
Picture Variant Variant description
IB-7302
IB-7302 32 inputs 24 V  DC / 5 ms
Order num. TXN 173 02
Teco code TXN 173 02
Categories TC700 - I / O Expansion Modules
Tags Sales and production discontinued
COM - System buses
TCL2 - system I/O bus 1x TCL2 slave
DI - Organization of binary inputs
Total number of binary inputs 32
Number of groups of binary inputs 2
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminals DI0 - DI32
Number of inputs in group 16
Common wire minus
Input type Type 1 (IEC)
Galvanic isolation of inputs from internal/peripheral circuits Yes, even between groups
Diagnostics indication of energized input by LED on module panel
Input voltage for log. 0 0 V DC; -15 V DC min; 5 V DC max.
Input voltage for log. 1 24 V DC; 15 V DC min.; 30 V DC max.
Input current at log. 1 (typ.) 3 mA
Delay from log. 0 to log. 1 5 ms
Delay from log. 1 to log. 0 5 ms
Insulation voltage between inputs and internal circuits 500 V
Insulation voltage between groups of inputs 500 V
Power supply
Nominal supply voltage (V) 24 V DC; Power supply from the system bus
Power consumption from the system source 1,8 W
Size and weight
Weight approx. 300 g
Product dimensions (width x height x depth) 30 x 198 x 137 mm
Operating conditions, product standards
Product standard ČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical object III, ČSN 33 0600: 1995
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, according to ČSN 33 2000-3: 1995 (mod IEC 364-3: 1993)
Degree of pollution 2, according to ČSN EN 61131-2
Overvoltage category installation II according to ČSN 33 0420-1
Type of device Built-in
Working position Vertical
Type of operation (operating frequency) Continuous
Ambient operating temperatures 0 ° C to + 55 ° C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission A, according to EN 55022: 1999 (mod CISPR22: 1997)
Emmisions - note In premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action.
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly description The installation of the module into the supporting frame of the TC700 system is performed according to TXV 004 02. The mechanical dimensions are given in the TXV 004 02 documentation.
Connection
Connection description The module is equipped with a connector that allows the customer to select and order the counterpart separately - removable connector straight, vertical, screw or screwless. The connection of the connector is shown in the picture.

Detailed connection data, principles of correct installation, examples of module connection and principles of increasing durability and reliability are given in the TXV 001 08.01 design manual.
Module operation
Module configuration The module is operated, set up and diagnosed from the Mosaic development environment.
Module diagnostics The basic diagnostic system of the module is a part of its standard software. It operates from module power on and operates independently of the user. Diagnostic error states of the module and connected peripheral modules of the assembly are signaled
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Notice Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

IB-7302 - Basic Documentation

124.53 kB, (CS, EN)
PDF

TC700 connectors - Basic documentation

105.65 kB

User manuals

PDF

TC700 - Tecomat programmable logic controlers (en)

5.19 MB, (EN)
  • IB–7302 binary input module - The IB-7302 binary input module has 32 binary inputs, 24 VDC, common pole, type 1. The inputs are in groups of 16, which are galvanically isolated from each other. The module is galvanically isolated from the other PLC circuits. The module input cir...

No data available.