Picture | Variant | Variant description |
---|---|---|
SC-1111.A |
The SC-1111.A module is a system communication module enabling the connection of RFox II wireless network modules or mutual wireless communication of several PLCs.
The module is operated by the RFoxMaster library in the Mosaic development environment.
TECOMAT FOXTROT central units allow to connect up to 6 SC-11xx system communication modules, which occupy channels CH5 - CH10
The module is operated by the RFoxMaster library in the Mosaic development environment.
TECOMAT FOXTROT central units allow to connect up to 6 SC-11xx system communication modules, which occupy channels CH5 - CH10
Order num. | TXN 111 11.A |
---|---|
Teco code | TXN 111 11.A |
Categories | RFox2 - System Modules, Foxtrot - Communication Modules (TCL2) |
Tags | - |
COM - Wireless network | |
---|---|
RFox2 wireless network | RFox2 Master |
Communication frequency band | 868,1 MHz |
Transmission power | +14 dBm |
Input sensitivity | –108 dBm |
Modulation type | 2-GFSK |
Communication speed | 50 kbps |
Transmission frequency | 868,1 MHz |
Power supply | |
Supply voltage, tolerances | 24 V DC, +25 %, –15 % |
Maximum power input | < 1 W |
Module thermal/power loss | 0,8 W |
Internal protection | Yes |
Size and weight | |
Weight approx. | 75 g |
Product dimensions (width x height x depth) | 18 x 90 x 58 mm |
Module width in multiples of M (17.5 mm) | 1M |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999) |
Protection class of electrical object | I, according to ČSN EN 61140: 2003 (idt IEC 61140: 2001) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP10B |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1: 2004 (mod IEC 60664-1: 1992) |
Overvoltage category installation | II, acc. ČSN EN 60664-1:2004 (mod IEC 606641:1992) |
Type of device | Module on DIN rail |
Working position | Any |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | -20 °C to + 55 °C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 ° C to + 85 ° C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | ČSN EN 55022 ed2:2007 (mod CISPR22:2005) |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.2: 2001 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Connection | |
Connection description |
An example of module connection is shown in the following figure. If the module is connected at the end of the TCL2 line, the terminator KB-0290 must be used. The module address on the TCL2 bus is set with the rotary switch. Any type designed for the 868 MHz band with an SMA connector (pin) can be used as an antenna. |
Connection of power and system communication | terminal block with screw terminal 2.5 mm2 |
Module operation | |
Commissioning | The module is operated as a system serial port, the settings are made in the Project Manager of the programming environment Mosaic see manual TXV 004 12. |
Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant Mosaic environment registers |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
Notice | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!! |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
SC-1111.A - Basic documentation
1.38 MB, (EN)
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot - EC Declaration of conformity
295.20 kB, (EN, RU, DE, UA)
- SC-1111-A - The SC-1111 module is a system communication module enabling the connection of RFox II wireless network modules or mutual wireless communication of several PLCs. The module is operated by the library in the Mosaic development environment. TECOMAT FO...
- Power dissipation of modules for calculation of switchboard heating - ...TXN 111 02 SC-1102; 1x CAN interface SC-1102 0,8 W TXN 111 11.A SC-1111-A; RF interface for RFox, radio type "A" SC-1111 0,8 W TXN 111 12.T...
No data available.