SC-1112.TTXN 111 12.T
SC-1112-T; RF interface for Wireless M-BUS, mode T
DI | |
---|---|
DO | |
AI | |
AO | |
COM | 1x TCL2 1x Wireless Mbus (T) |
SENSOR |
Picture | Variant | Variant description |
---|---|---|
SC-1112.T |
SC-1112-T; RF interface for Wireless M-BUS, mode T
RFox2 master on DIN rail (1M) The SC-1112.T module is a system communication module enabling the extension of the central unit by receiving and transmitting RF packets via the Wireless M-Bus protocol in "T" and "S" modes (EN 13757-4). The operation of this module is realized by the WMBusLib library in the Mosaic development environment. TECOMAT FOXTROT central units allow the connection of up to 6 SC-11xx system communication modules, which occupy channels CH5 - CH10.
RFox2 master on DIN rail (1M) The SC-1112.T module is a system communication module enabling the extension of the central unit by receiving and transmitting RF packets via the Wireless M-Bus protocol in "T" and "S" modes (EN 13757-4). The operation of this module is realized by the WMBusLib library in the Mosaic development environment. TECOMAT FOXTROT central units allow the connection of up to 6 SC-11xx system communication modules, which occupy channels CH5 - CH10.
Order num. | TXN 111 12.T |
---|---|
Teco code | TXN 111 12.T |
Categories | Foxtrot - Communication Modules (TCL2) |
Tags | - |
COM - Wireless network | |
---|---|
Communication frequency band | Mode T: 868,95 MHz, Mode S: 868,3 MHz |
Transmission power | +14 dBm |
Input sensitivity | Mode T: -105 dBm Mode S: -109 dBm |
Modulation type | 2-FSK |
Communication speed | Mode S: 32,768 kbps/2-FS, Mode T: 100 kbps/2-FSK |
Power supply | |
Supply voltage, tolerances | 24 V DC, +25 %, –15 % |
Typical power input | 1 W |
Maximum power input | < 1 W |
Module thermal/power loss | 0,8 W |
Maximum current consumption (mA) | 85 mA |
Internal protection | Yes |
Size and weight | |
Weight approx. | 75 g |
Module width in multiples of M (17.5 mm) | 1M |
Product dimensions (width x height x depth) | 18 x 95 x 58 mm |
Operating conditions, product standards | |
Product standard | ČSN EN 60730-1 ed. 3:2012 (mod IEC 60730-1:2010) |
Protection class of electrical object | I, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016) |
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) | IP20 |
Operating areas | Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005) |
Degree of pollution | 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007) |
Overvoltage category installation | II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007) |
Type of device | Module on DIN rail |
Working position | Any |
Type of operation (operating frequency) | Continuous |
Ambient operating temperatures | -20 °C to + 55 °C |
Operating temperature maximum (° C) | +55°C |
Operating temperature minimum (° C) | -20°C |
Operating relative humidity | from 10 % up to 95 % without condensation |
Operating atmospheric pressure | min. 70 kPa (<3,000 m above sea level) |
Storage temperatures | –25 °C to +70 °C |
Electromagnetic compatibility, Mechanical endurance | |
Electromagnetic compatibility / Emission | B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015) |
Electromagnetic compatibility / Immunity | min. according to ČSN EN 60730-1 ed.3: 2012 |
Sinusoidal vibration endurance | 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.) |
Packaginng, transportation, storage | |
Description | The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C |
Connection | |
Connection description | An example of module connection is shown in the following figure. If the module is connected at the end of the TCL2 line, the terminator KB-0290 must be used. The address of the module on the TCL2 bus is set with a rotary switch. Any type designed for the 868 MHz band can be used as an antenna by terminating with the SMA connector (pin). |
Connection of power and system communication | terminal block with screw terminal 2.5 mm2 |
Module operation | |
Module configuration | The module is operated, set up and diagnosed from the Mosaic development environment. |
Commissioning | The module is operated as a system serial port, the settings are made in the Project Manager of the programming environment Mosaicviz manual TXV 004 12. |
Module diagnostics | The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment. |
Maintenance | |
Description | The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected. |
Warning | Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures. |
Warranty | |
Generally | Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s. |
Notice | You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change. |
HW documentation
SC-1112.T - Basic documentation
231.60 kB, (CS, EN)
SC-1112 - Basic documentation
586.81 kB, (EN)
Files for designers
Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.
20.49 MB
Foxtrot 2 - element library for SchemataCAD, v. 2024/01
6.79 MB
EC - Declaration of Conformity
Foxtrot 2 - EC Declaration of conformity (en)
590.15 kB, (EN, RU, DE, UA)
- Power dissipation of modules for calculation of switchboard heating - ...C-1111-A; RF interface for RFox, radio type "A" SC-1111 0,8 W TXN 111 12.T SC-1112.T; RF interface for Wireless M-BUS, mode T SC-1112 0,8 W TXN 111 31...