CP-2970TXN 129 70

cp-2970

DI 21x DI
DO 18x DO
AI 20x AI
AO 6x AO
COM
SENSOR
Picture Variant Variant description
CP-2970
CP-2970
Order num. TXN 129 70
Teco code TXN 129 70
Categories Foxtrot 2 - Open Frame, basic and expansion modules
Tags -
System parameters of the central unit
Row of central unit I
User program memory 1 MB
Memory for user variables / including RETAIN variables 320 kB/48 kB
Instruction length 4 Byte
Backup of program source code in PLC Yes, optional in Mosaic
On-line program change in PLC Yes, including I / O configuration change
DataBox - additional internal data memory 128/257 kB, optional
File system - Internal Drive in PLC 128 MB, journaling file system
File system - RAM disk PLC 16 MB
File System - USB Flash Drive Supported
File system - Micro SD card supported (except for variants with WLAN1)
Optional memory card slot microSD - Card Slot (<= 1TB)
Cycle time per 1k of logic instructions 0,036 ms
Cycle time for 1k integer operations 0,044 ms
Cycle time for 1k floating point operations 0,043 ms
Development environment Mosaic v2018.2 or higher
Programming languages ST, IL, LD, FBD, SFC, CFC
RTC - Real time circuit No
RTC - Backup time typ. 500 hours
Integrated Web server Yes
Integrated Datalogger Yes
Access to PLC variables via web API Yes
COM - Communication - IP/Ethernet
Ethernet 10/100 Mb (ETHx) 2
WLAN1 (internal, optional) 1
WLAN2 (external via USB host, optional) 1
LTE interface (LTEx, optional) 1
Available system modes on ETH and WLAN UNI, PC, PLC, PLD
Available system modes on LTE UNI - Exchange over UDP, TCP and support SSL / TLS encryption PC - EPSNET UDP / EPSNET TCP
TCP / IP protocol Yes
UDP protocol No
HTTPS protocol No
HTTP protocol No
Protocol MODBUS/TCP No
SMTP protocol No
IEC 60870-5-104 protocol No
REST API No
COM - USB
USB devices interface 1x micro-USB
USB host interface 1x USB-A
Available system modes on USB PC
COM - Serial channels
max. number of optional serial channels in the basic module 4
number of slots for optional submodules with interface (MR-013x) 2
max. number of expanding serial channels on the TCL2 bus 6
Number of internal RS-232 serial channels 1
Available system modes on CH5-10 UNI, CSJ (CAN)
Modbus RTU / ASCII master protocol No
Modbus protocol RTU/ASCII slave No
Profibus DP master protocol (<180 kbit/s) No
COM - System buses
TCL2 - system I/O bus 1x TCL2 master
TCL2 - Range of one branch of the system I/O bus 10 I / O modules + 4 operator panels + 6 serial channels
CIB - Common Installation Bus (R): Installation I/O bus 1x CIB master (100 mA)
CIB - Address range of one branch of the installation bus 32 CFox I/O modules
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminals 18x DI (AI/DI0-AI/DI17)
Common wire minus
Input type Type 2 (IEC) - passive
Galvanic separation of inputs from internal circuits No
Diagnostics signaling of excited input in Mosaic
Pulse input overload capacity max. 30 V (t < 10 ms)
Input voltage for log. 0 0 V DC; -5 V DC min.; +5 V DC max.
Input voltage for log. 1 24 V DC; 15 V DC min.; 30 V DC max.
Input current at log. 1 (typ.) 2,5 mA typ.
Delay from log. 0 to log. 1 1 ms
Delay from log. 1 to log. 0 1 ms
The minimum width of the captured pulse 500 μs
Frequency of measurement PLC cycle
DI - Parameters of DC binary inputs (group B)
Parameters valid for inputs on the terminals 4x DI/HSC (AI/DI8-AI/DI11)
Number of inputs in group 4
Common wire minus
Input type (IEC) Type 2 (IEC) - passive
Combined input type DI / HSC High Speed Counter
DI - Parameters of binary inputs DC (group C)
Parameters valid for inputs on the terminals 2x DI (DI19, DI20)
Number of inputs in group 2
Common wire minus
Input type (IEC) Type 2 (IEC) - passive
Galvanic separation of inputs from internal circuits No
Diagnostics alarm signaling Mosaic environment
Input voltage for log. 0 0 V DC; -5 V DC min.; +5 V DC max.
Input voltage for log. 1 +24 V DC; min. +15 V DC; max. +30 V DC
Input current at log. 1 (typ.) 5 mA at 24 V DC
Delay from log. 0 to log. 1 1 ms
Delay from log. 1 to log. 0 1 ms
The minimum width of the captured pulse 1 ms
Izolační napětí 2500 V AC
DI - Parameters of binary AC inputs
Parameters valid for AC inputs on the terminals 2x DI 230 V AC (DI18)
Total number of binary AC inputs 1
Number of groups of AC inputs 1
Number of AC inputs in group 1
Common wire L
Input type 230 V AC
Galvanic isolation of internal circuits Yes
Input voltage for log. 0 0 V AC min., 120 V AC max.
Input voltage for log. 1 230 V AC typ., 200 V AC min., 250 V AC max.
Input current at log. 1 (typ.) 5 mA typ.
Delay from log. 0 to log. 1 10 ms
Delay from log. 1 to log. 0 10 ms
DO/RO - Organization of binary outputs
Total number of binary outputs 18
DO - Parameters of SSR (solid state relay) outputs (group A)
Parameters valid for the terminals 4x DO (DO12-DO15)
Galvanic separation of the output Yes
Switching voltage (V) min. 20VAC, max. 260VAC
Switching current (A) max. 1A; min. 5mA
Internal protection, output treatment No
Insulation voltage between groups of outputs 3750 V AC
RO - Parameters of binary relay outputs (group A)
Parameters valid for the terminals 16x DO (DO0-DO15)
Number of relay outputs 15
Output type electromechanical relay, unprotected output
Contact type NO - Normally Open
Diagnose Alarm signaling on panel module
Switching current 16 A max., 100 mA min.
Switching voltage 250 V AC max., 5 V AC min., 30V DC max.
Contact closing time typ. 10 ms
Contact opening time typ. 4 ms
Short-circuit protection No
AI - Organization of analog inputs
Number of analog input groups 4
Organization of analog inputs into groups 15x AI/DI (AI/DI0-AI/DI14); 2x AI (AI15-AI16)
1x AI (AI17)
2x AI (AI19-AI20)
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminals 15x AI (AI0 ÷ AI14)
Voltage 0-10 V
Voltage 0-5 V
Voltage 0-2 V
Voltage 0 -1 V
Voltage –20 to +50 mV / 19 µV
Voltage –20 to +100 mV / 38 µV
Ccurrent 0 to 20 mA / 8,059 μA
Current 4-20 mA
Passive sensor Pt1000, W100 = 1,385 (-90 to +400 ° C)
Passive sensor Ni1000, W100 = 1,500 (–60 to +200 ° C)
Passive sensor Resistance transmitter 0-2 kOhm
Passive sensor Resistance transmitter 0-200 kOhm
Passive sensor KTY81-121; PTC thermistor (-55 to + 125 °C)
AI - Analog Input Ranges (Group B)
Parameters valid for inputs on the terminals 2x AI (AI15, AI16)
Voltage 0 to 10 V / 2,579 mV
Voltage 0 to 5 V / 2,726 mV
Voltage 0 to 2 V / 805.9 μV
Voltage 0 to 1 V
Voltage –20 to +50 mV / 19 µV
Voltage –20 to +100 mV / 38 µV
Ccurrent 0 to 20 mA / 8,059 μA
Current 4-20 mA
AI - Analog Input Ranges (Group C)
Parameters valid for inputs on the terminals 1x AI (A17)
Voltage 0-2 V
Voltage 0 to 1 V
Voltage –20 to +50 mV / 19 µV
Voltage –20 to +100 mV / 38 µV
Thermocouple Type J (-210 ° C to 1200 ° C)
Thermocouple Type K (–200 to +1372 ° C)
Thermocouple Type R (-50 to +1768 ° C)
Thermocouple Type N (-200 ° C ÷ 1300 ° C)
Thermocouple Type T (-200 ° C ÷ 400 ° C)
Thermocouple Type B (250 ° C ÷ 1820 ° C)
Thermocouple Type S (-50 ° C ÷ 1768 ° C

HW documentation

PDF

CP-297x - User's Guide

662.25 kB
PDF

CP-2972_clamps

57.22 kB
PDF

CP-297x - technical drawing 1

394.28 kB

Files for designers

DWG

CP-297x - technical drawing DWG 1

47.39 kB
DXF

CP-297x - technical drawing DXF 1

313.39 kB

EC - Declaration of Conformity

PDF

Foxtrot 2 - EC Declaration of conformity (en)

590.15 kB, (EN, RU, DE, UA)
  • CP-2970, basic module for OEM applications - ..., air handling units, cooling units, automatic boilers and other heat equipments.   Basic description The CP-2970 module is a complete Foxtrot series control system designed to be built into the target product. The module is fully...
  • C-IR-0303M - ...cuits - both for common installations in the field of M&R and for the OEM segment - variant addition of heating circuits for CP-2970 / CP-1970 used as a control system for heat pumps and similar devices.   Po...

No data available.