SC-1112.TTXN 111 12.T

SC-1112-T; RF interface for Wireless M-BUS, mode T

DI
DO
AI
AO
COM 1x TCL2
1x Wireless Mbus (T)
SENSOR
Picture Variant Variant description
SC-1112.T
SC-1112-T; RF interface for Wireless M-BUS, mode T
RFox2 master on DIN rail (1M) The SC-1112.T module is a system communication module enabling the extension of the central unit by receiving and transmitting RF packets via the Wireless M-Bus protocol in "T" and "S" modes (EN 13757-4). The operation of this module is realized by the WMBusLib library in the Mosaic development environment. TECOMAT FOXTROT central units allow the connection of up to 6 SC-11xx system communication modules, which occupy channels CH5 - CH10.
Order num. TXN 111 12.T
Teco code TXN 111 12.T
Categories Foxtrot - Communication Modules (TCL2)
Tags -
COM - Wireless network
Communication frequency band Mode T: 868,95 MHz, Mode S: 868,3 MHz
Transmission power +14 dBm
Input sensitivity Mode T: -105 dBm Mode S: -109 dBm
Modulation type 2-FSK
Communication speed Mode S: 32,768 kbps/2-FS, Mode T: 100 kbps/2-FSK
Power supply
Supply voltage, tolerances 24 V DC, +25 %, –15 %
Typical power input 1 W
Maximum power input < 1 W
Module thermal/power loss 0,8 W
Maximum current consumption (mA) 85 mA
Internal protection Yes
Size and weight
Weight approx. 75 g
Module width in multiples of M (17.5 mm) 1M
Product dimensions (width x height x depth) 18 x 95 x 58 mm
Operating conditions, product standards
Product standard ČSN EN 60730-1 ed. 3:2012 (mod IEC 60730-1:2010)
Protection class of electrical object I, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989) IP20
Operating areas Normal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution 1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installation II, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of device Module on DIN rail
Working position Any
Type of operation (operating frequency) Continuous
Ambient operating temperatures -20 °C to + 55 °C
Operating temperature maximum (° C) +55°C
Operating temperature minimum (° C) -20°C
Operating relative humidity from 10 % up to 95 % without condensation
Operating atmospheric pressure min. 70 kPa (<3,000 m above sea level)
Storage temperatures –25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / Emission B, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Electromagnetic compatibility / Immunity min. according to ČSN EN 60730-1 ed.3: 2012
Sinusoidal vibration endurance 10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
Description The module is packed in a paper box. This documentation is also part of the package. The outer packaging is carried out according to the scope of the order and the method of transport in a transport package provided with labels and other data necessary for transport. The product must not be exposed to direct weather conditions during transport and storage. Malting of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Connection
Connection description An example of module connection is shown in the following figure. If the module is connected at the end of the TCL2 line, the terminator KB-0290 must be used. The address of the module on the TCL2 bus is set with a rotary switch. Any type designed for the 868 MHz band can be used as an antenna by terminating with the SMA connector (pin).
Connection of power and system communication terminal block with screw terminal 2.5 mm2
Module operation
Module configuration The module is operated, set up and diagnosed from the Mosaic development environment.
Commissioning The module is operated as a system serial port, the settings are made in the Project Manager of the programming environment Mosaicviz manual TXV 004 12.
Module diagnostics The basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
Description The module does not require any maintenance under general installation conditions. The operations in which a part of the module has to be dismantled must always be carried out with the supply voltage disconnected.
Warning Because the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures.
Warranty
Generally Warranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
Notice You must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

HW documentation

PDF

SC-1112.T - Basic documentation

231.60 kB, (CS, EN)
PDF

SC-1112 - Basic documentation

586.81 kB, (EN)

Files for designers

ZIP

Foxtrot 2 - library of elements in DXF and DWG formats, v. 2024/01.

20.49 MB
KNI

Foxtrot 2 - element library for SchemataCAD, v. 2024/01

6.79 MB

EC - Declaration of Conformity

PDF

Foxtrot 2 - EC Declaration of conformity (en)

590.15 kB, (EN, RU, DE, UA)